    Pointek CLS300 - Digital
    Pointek CLS300 (digital version) is an inverse frequency shift capacitance level and material detection switch with optional rod/cable choices and configurable output. It is ideal for detecting liquids, solids, slurries, foam, and interfaces in demanding conditions where high pressure and temperatures are present and has the ability to tune out buildup on the probe. The digital version includes PROFIBUS PA, an LCD display, and advanced diagnostic features.

    7ML5660-.....-....
    CLS300,DIGITAL,ROD VERSN,THREAD/FLANGE
    7ML5661-.....-....
    CLS300,DIGITAL,CABLE VERSN,THREAD/FLANGE
    7ML5662-.....-....
    CLS300,DIGITL,HIGH TEMP ROD,THREAD/FLANG


    Related products

    Part NumberDescription
    7ML1830-1APEASY AIMER II, ALUMINIUM, 3/4 INCH NPT WITH 1 INCH GALVANIZED COUPLING
    7ML1830-1JACABLE GLAND, 1/2" NPT, General Purpose DIP
    7ML1830-1JBCABLE GLAND, 1/2" NPT, explosion proof
    7ML1830-1JCM20 x 1.5 cable gland (general use and dust explosion protection)
    7ML1830-1JDCABLE GLAND, M20 x 1.5 HF, (EP)
    7ML1830-1JETest Magnet
    7ML1830-1JFAMPLIFIER / POWER SUPPLY DIGITAL VERSION
    7ML1830-1JKLCD DISPLAY FOR CLS 200, DIGITAL
    7ML1930-1AQOne metallic cable gland M20x1.5, rated -40掳C (-40掳F) to +80掳C (+176掳F) with integrated shield connection (available for PROFIBUS PA)
    A5E01163688Kit, 316L stainless steel cable extension, 1 Meter, CLS300/LC300
    A5E01163689Kit, 316L stainless steel cable extension, 3 Meter, CLS300/LC300
    A5E01163690Kit, 316L stainless steel cable extension, 5 Meter, CLS300/LC300
    A5E01163691Kit, 316L stainless steel cable extension, 10 Meter, CLS300/LC300
    A5E01163693Kit, 316L stainless steel cable extension, 15 Meter, CLS300/LC300
    A5E01163695Kit, 316L stainless steel cable extension, 20 Meter, CLS300/LC300
    A5E01163698Kit, 316 stainless steel PFA cable extension, 3 METER, CLS300
    A5E01163699Kit, 316 stainless steel PFA cable extension, 5 METER, CLS300
    A5E01163700Kit, 316 stainless steel PFA cable extension, 10 METER, CLS300
    A5E01163701Kit, 316 stainless steel PFA cable extension, 15 METER, CLS300
    A5E01163702Kit, 316 stainless steel PFA cable extension, 20 METER, CLS300
    A5E01163719Kit, 316L stainless steel rod 180 mm (7.09")
    A5E01163720Kit, 316L stainless steel rod 330 mm (12.99")
    A5E01163721Kit, 316L stainless steel rod 580 mm (22.83")
    A5E01163722Kit, 316L stainless steel rod 830 mm (32.68")
    A5E01163723Replacement electronics with driver, CLS300 standard. For use with rod or Cable versions with maximum length of 5 m
    A5E01163724Replacement electronics with driver, CLS300 standard. For use with Cable versions with minimum length of 5 m
    A5E01163725Replacement electronics with driver, CLS300 Digital. For use with rod or Cable versions with maximum length of 5 m
    A5E01163726Replacement electronics with driver, CLS300 Digital. For use with Cable versions with minimum length of 5 m
    A5E01163727KIT, Spare 316L stainless steel weight, CLS/LC300, cable version
    A5E03251683Kit, CLS300 standard, transmitter

    Benefits
    Active-Shield technology so measurement is unaffected by material buildup or nozzle interference in active shield section
    Performs in extremely abrasive conditions because of solid rod construction
    Push-button calibration, full-function diagnostics
    High sensitivity allows installation in a wide range of liquids, solids or slurry applications
    Integral LCD display allows for easy menu-driven setup
    PROFIBUS PA communication (SIMATIC PDM compatible)

    Application
    Pointek CLS300 digital version provides an integral LCD display for stand-alone use, with PROFIBUS PA communication
    (Profile version 3.0, Class B) when required. Solid-state switch alarm is standard.

    The robust design of CLS300 makes it specifically applicable for heavy solids applications where abrasive materials occur as in the mining industry.

    The fully potted electronics are unaffected by condensation, dust or vibration.

    Wetted parts are made of stainless steel with a PFA shield for high chemical resistance, and of ceramic and stainless steel for high temperature version. Materials with low or high dielectric constants can be accurately detected. The unique Active Shield suppresses interference from material buildup or long installation nozzles.

    The unique modular design of the Pointek CLS300 provides a wide range of configurations, process connections, extensions and approvals to meet the temperature and pressure requirements of specific applications. The modular design makes ordering easier and reduces stocking requirements. A wide range of probe configurations are available, including rod and cable versions.

    Key Applications: liquids, slurries, bulk solids, relatively high pressure and temperature, hazardous areas, milling and mining applications

    Configuration

    Pointek CLS300 - Digital

    Pointek CLS300 - Digital

    Technical specifications

    Pointek CLS300 Digital


    Mode of operation


    Measuring principle

    Inverse frequency shift capacitive level detection

    Input


    Measured variable

    Change in picoFarad (pF)

    Output


    Solid-state output


    • Output

    Galvanically isolated

    • Protection

    Against reversed polarity (bipolar)

    • Max. switching voltage
    • 30 V (DC)
    • 30 V peak (AC)
    • Max. load current

    82 mA

    • Voltage drop

    < 1 V, typical at 50 mA

    • Time delay (pre or post switching)

    Programmable by user (0 ... 100 s)

    Fail-safe mode

    Min. or max.

    Connection

    Removable terminal block

    Accuracy


    Resolution


    • Min. sensitivity (pF)

    1 % change in actual capacitance

    • Max. temperature error

    0.2 % of actual capacitance value

    Rated operating conditions1)


    Installation conditions


    • Location

    Indoor/outdoor

    Ambient conditions


    • Ambient temperature

    ‑40 ... +85 °C (‑40 ... +185 °F)2)

    • Storage temperature

    ‑40 ... +85 °C (‑40 ... +185 °F)

    Medium conditions

    Liquids, bulk solids, slurries, interfaces, and applications with viscous materials

    • Relative dielectric constant εr

    Min. 1.5

    • Process temperature

    • Rod/Cable version

    -40 ... +200 °C (-40 ... +392 °F)2)

    • High Temperature version

    -40 ... +400 °C (-40 ... +752 °F)

    • Process pressure3)

    -1 ... +35 bar g (-14.6 ... +511 psi g)

    Design


    Material (enclosure)

    Powder-coated aluminum with gasket

    Degree of protection

    Standard: Type 4/NEMA 4/IP65
    Optional: Type 4/NEMA 4/IP68

    Cable inlet

    2 x M20 x 1.5 thread (option: 2 x ½" NPT conduit entry including 1 plugged entry)

    Controls and displays


    Local display

    LCD

    Configuration

    • Locally, using 3 button keypad (for standalone operation)
    • Remotely, using SIMATIC PDM (for installation on a network)

    Power supply


    Bus voltage (at process connection)

    • Standard: 12 ... 30 V DC
    • Intrinsically Safe: 12 ... 24 V DC

    Current consumption

    12.5 mA

    Certificates and approvals


    General Purpose

    CSA, FM, CE, UKCA, RCM

    Dust Ignition Proof

    ATEX II 1/2 D, 2 D IP6X T100 °C

    UKEX II 1/2 D Ex ia/tb [ia Da] IIIC TX
    Da/Db

    Flameproof Enclosure With IS Probe

    ATEX II 1/2 G EEx d[ia] IIC T6 ... T4
    ATEX II 1/2 D T100 °C

    UKEX II 1/2 G Ex ia/db [ia Ga] IIC TX Ga/Gb
    UKEX II 1/2 D Ex ia/tb [ia Da] IIIC TX Da/Db

    Dust Ignition Proof With IS Probe

    CSA/FM Class II, Div. 1,
    Groups E, F, G

    CSA/FM Class III T4

    Intrinsically Safe4)

    ATEX II 1 G EEx ia IIC T6 ... T4
    ATEX II 1/2 D, 2 D IP6X T100 °C

    UKEX II 1 G Ex ia IIC TX Ga
    UKEX II 1/2 D Ex ia IIIC TX Da/Db

    CSA/FM Class I, Div. 1,
    Groups A, B, C, D
    CSA/FM Class II, Div. 1,
    Groups E, F, G
    CSA/FM Class III T4

    Non-incendive

    CSA/FM Class I, Div. 2,
    Groups A, B, C, D
    CSA/FM Class II, Div. 2,
    Groups F, G
    CSA/FM Class III T4 or T6

    Explosion Proof with IS Probe

    CSA/FM Class I, Div. 1,
    Groups A, B, C, D
    CSA/FM Class II, Div. 1,
    Groups E, F, G
    CSA/FM Class III T4

    Marine

    Lloyds Register of Shipping, Categories ENV1, ENV2, and ENV5

    Others

    Pattern Approval (China)

    Communication

    PROFIBUS PA
    (IEC 61158 CPF3 CP3/2)

    Bus physical layer: IEC 61158-2 MBP-(IS)

    Device profile: PROFIBUS PA profile for Process Control Devices Version 3.0, Class B

    FISCO field device


    Quality Pointek CLS300 - Digital for sale